Cleaning and treating a new commercial system |
Fernox Product Catalogue |
Commercial Range Leaflet |
Commercial Chemicals |
For optimum results, the entire system should be completely drainable. Cleaner F3 should be dosed at a concentration of 0.5%. The product can be introduced into the system via a suitable point such as a dosing pot. For pre-commission cleaning, circulate Cleaner F3 in the system for at least one hour at normal operating temperature. To remove sludge from existing systems, circulate under normal operating conditions, for up to 7 days until acceptable flow around the system has been achieved. Additional/ repeat applications of Cleaner F3 may be necessary if systems are heavily sludged. Drain and flush with cold water until the water is clear and the Cleaner F3 has been rinsed from the system. Finally, add an appropriate Fernox inhibitor such as Protector F1 to prevent further corrosion damage and scale deposits.
Colour: Amber
Odour: Faintly aromatic
Form: Liquid
pH (conc): 6.6
pH (in-use) 6.5 – 7.7
SG: 1.116 @ 20°C
Fernox Cleaner F3 is supplied in 10 litre containers. Fernox Cleaner F3 is classified as non-hazardous, but as with all chemicals: Keep out of reach of children. Do not mix with other chemicals. In case of contact with eyes or skin, rinse immediately with plenty of water.