How to prevent corrosion?

Algae in feed and expansion cisterns Leathery skins or films of algae on the surface of expansion cisterns in open vented systems are caused by fungal mould growths. It occurs when the expansion cistern is not properly covered causing dust, insects and spores to be able to enter the water.

Algae in feed and expansion cisterns
Underfloor heating systems are also susceptible to microbial growth due to the lower temperatures at which these systems operate.

Gas in the system
Microbiological fermentation in a system could result in flammable gas. Methane gas, which burns with a blue flame, is most often found.Hydrogen sulphide (emitting a ‘bad egg’ smell) may also occur, and is associated with the presence of corrosive sulphate-reducing bacteria.

Bacterial or yeast infestations caused by organisms entering the system from the supply water; debris in new systems or through air contact in open expansion cisterns can also occur.

What should be done?

To combat algae in open vented systems, empty the cistern and disinfect with Fernox AF-10 Biocide or Fernox LP Sterox. Refill the tank, adding the correct dose of AF-10 Biocide (refer to the instructions on the container)and top up the concentration levels of Protector F1. Ensure the tank is fitted with a purpose-made lid to prevent future contamination of the tank.

When there is gas in a system,use Fernox AF-10 Biocide to control microbiological growths and prevent gas build-up. Where contamination is significant,several repeat doses of biocide may be required: in such situations, it may be appropriate to drain and retreat the entire system.

Bacterial contamination in air and ground source heat pumps
When there is bacterial contamination in air and ground source heat pumps, Fernox HPCleaner can be used.

Before use, it should be diluted using no more than 600 litres ofmains water per one litre of HPCleaner (equivalent to 600 metres of 40mm pipework). The ground collector must be flushed out with fresh mains water before being filled with the diluted product.Having circulated the HP Cleaner for at least one hour, after whichit should be flushed out until thewater runs clear. Fill the ground collector with Fernox HP-5 /HP-5c or HP-15 / HP-15c depending on the level of frost protection required.

Share:

More posts:

How to repair system leaks

Leaks in water systems can result from external frost damage, dry solder joints, accidental perforation during maintenance or decoration, or internal corrosion. Sealing internal leaks (central heating systems only) Small leaks, including pressure drops on combination boilers and other sealed systems, can be repaired using Fernox Leak Sealer F4. Each Leak Sealer F4 product treats 130 litres or up to

Read More »

How to reduce fuel wastage in heating systems?

Soft and hard limescale on radiator walls can drastically reduce their ability to heat rooms efficiently. The problem often revolves around the boiler heat exchanger where the temperature is hottest, but deposits in radiators and pipework also lessen the effectiveness of the whole system. It is therefore important to consider the whole central heating system when checking and establishing why

Read More »

Country