How to prevent corrosion?

Algae in feed and expansion cisterns Leathery skins or films of algae on the surface of expansion cisterns in open vented systems are caused by fungal mould growths. It occurs when the expansion cistern is not properly covered causing dust, insects and spores to be able to enter the water.

Algae in feed and expansion cisterns
Underfloor heating systems are also susceptible to microbial growth due to the lower temperatures at which these systems operate.

Gas in the system
Microbiological fermentation in a system could result in flammable gas. Methane gas, which burns with a blue flame, is most often found.Hydrogen sulphide (emitting a ‘bad egg’ smell) may also occur, and is associated with the presence of corrosive sulphate-reducing bacteria.

Bacterial or yeast infestations caused by organisms entering the system from the supply water; debris in new systems or through air contact in open expansion cisterns can also occur.

What should be done?

To combat algae in open vented systems, empty the cistern and disinfect with Fernox AF-10 Biocide or Fernox LP Sterox. Refill the tank, adding the correct dose of AF-10 Biocide (refer to the instructions on the container)and top up the concentration levels of Protector F1. Ensure the tank is fitted with a purpose-made lid to prevent future contamination of the tank.

When there is gas in a system,use Fernox AF-10 Biocide to control microbiological growths and prevent gas build-up. Where contamination is significant,several repeat doses of biocide may be required: in such situations, it may be appropriate to drain and retreat the entire system.

Bacterial contamination in air and ground source heat pumps
When there is bacterial contamination in air and ground source heat pumps, Fernox HPCleaner can be used.

Before use, it should be diluted using no more than 600 litres ofmains water per one litre of HPCleaner (equivalent to 600 metres of 40mm pipework). The ground collector must be flushed out with fresh mains water before being filled with the diluted product.Having circulated the HP Cleaner for at least one hour, after whichit should be flushed out until thewater runs clear. Fill the ground collector with Fernox HP-5 /HP-5c or HP-15 / HP-15c depending on the level of frost protection required.

Share:

More posts:

Does Fernox Cleaner F3 need to be flushed out of the system?

Fernox Cleaner F3 should ideally circulate through the system for at least one hour, or up to a week. Afterward, it should be drained, and the system flushed and cleaned before adding Fernox Protector F1 or Protector + Filter Fluid, together with a Fernox TF1 Filter, to protect the system from further corrosion and scale formation.

Read More »

How to clean a heating system?

Normally a treatment will last the life of the system but an annual check to determine whether further dosing is necessary is recommended. If the system is drained, it will need to be re-treated with a further full dose of Protector. You can check if the system is properly dosed using a Fernox Protector Test Kit.

Read More »

Country